100% Genuine. 100,000+ Parts in Stock. Ready to Ship.

  • en

The GE Fanuc IC693PWR322, also cataloged as the IC693PWR322 Standard Power Supply, operates as a dedicated hardware component for internal backplane power distribution and DC/DC conversion within Series 90-30 platforms.

Hardware Specifications

Parameter Specification
Model IC693PWR322
Brand GE Fanuc Emerson
Origin USA
Weight 1.25 lbs (0.57 kg)
Dimensions Standard Series 90-30 power supply slot width
Operating Temp 0 to 60 deg C
Power Consumption 50 W with VDC input
Total Output Power 30 Watts total capacity
Nominal Input Voltage 24 VDC / 48 VDC
Input Voltage Range Start: 21 to 56 VDC; Run: 18 to 56 VDC
5 VDC Output Power 15 Watts maximum
Isolated +24 VDC Output 20 Watts maximum
Relay +24 VDC Output 15 Watts maximum
Inrush Current 4 A peak, 100 ms maximum
Holdup / Ride-Through Time 14 ms minimum holdup time; 10 ms minimum ride-through time
Onboard Diagnostic LEDs PWR, OK, RUN, BATT
Serial Interface RS-485 serial port

Backplane Bus Communication Velocity & Power Distribution

The IC693PWR322 power module delivers stable DC operating voltages across the Series 90-30 backplane, maintaining system backplane bus communication velocity and processing continuity during DC supply line fluctuations. It converts a nominal 24/48 VDC input into three regulated outputs: +5 VDC logic power, +24 VDC isolated power, and +24 VDC relay power up to a total load of 30 Watts. Firmware flash compatibility and internal diagnostic monitoring are supported through front-panel LEDs (PWR, OK, RUN, BATT) and an integrated RS-485 serial interface. An internal energy storage stage provides a 14 ms minimum holdup time to prevent CPU logic resets under transient power dropouts.

Frequently Asked Questions

Q: What are the input DC voltage operating boundaries for the IC693PWR322?

A: The module requires 21 to 56 VDC to initiate system start-up and continues operation across a running input voltage range of 18 to 56 VDC.

Q: How is the maximum output power distributed across the internal supply rails?

A: The module provides up to 30 Watts total output power, divided into +5 VDC logic power (15 W max), isolated +24 VDC power (20 W max), and relay +24 VDC power (15 W max).

Q: What peak inrush current must be accounted for during system power-up?

A: The power supply generates a peak inrush current of 4 A with a maximum duration of 100 ms at initial energization.

Field Installation Guidelines

  1. Isolate primary field DC power sources before mounting or removing the power supply from the baseplate rack.
  2. Insert the IC693PWR322 into the left-most slot of the Series 90-30 baseplate rack, ensuring complete engagement with the backplane connector.
  3. Secure the top and bottom mounting screws to ground the module housing against the baseplate chassis ground.
  4. Wire input power leads (24/48 VDC nominal) to the designated screw terminals using appropriate copper conductor gauges.
  5. Route primary DC input power cables away from low-voltage communication and analog input wiring to prevent noise coupling.

What's clients say about us