The GE Fanuc IC695ALG704, also cataloged as the IC695ALG704 Analog Output Module, operates as a dedicated hardware component for multi-range signal generation and loop actuator control within PACSystem RX3i platforms.
| Parameter | Specification |
|---|---|
| Model | IC695ALG704 |
| Brand | GE Fanuc Emerson |
| Origin | USA |
| Weight | 0.50 lbs (0.23 kg) |
| Dimensions | Single-slot RX3i module width |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | 375 mA at 3.3 VDC backplane bus; 160 mA at 24 VDC isolated supply (4.8 W maximum dissipation) |
| Output Channels | 4 non-isolated channels |
| Output Signal Ranges | +/-10 VDC, 0 to 10 VDC, 0 to 20 mA, 4 to 20 mA |
| Signal Resolution | +/-10 V: 15.9 bits; 0 to 10 V: 14.9 bits; 0 to 20 mA: 15.9 bits; 4 to 20 mA: 15.6 bits |
| Output Load Limits | Current: 850 Ohms maximum (10 uH max reactance); Voltage: 1 uF max load reactance |
| Update Rate & Settling Time | 8 ms update rate; 2 ms settling time (0 to 95%) |
| Calibrated Accuracy | 0.15% of full scale at 25 deg C; 0.30% of full scale at 60 deg C |
| Output Protection | Voltage outputs withstand -30 VDC for 60 s, +30 VDC for 1 h |
| External Power Input | 19.2 to 30 VDC (24 VDC nominal) |
| Data Formats | IEEE 32-bit floating point; 16-bit integer in a 32-bit field |
The IC695ALG704 interfaces directly with the RX3i PCI backplane bus to execute high-speed data transfers with minimal processing latency. Channel data update rates are maintained at 8 ms across all four output paths, utilizing IEEE 32-bit floating point or 16-bit integer formatting. Firmware flash compatibility requires RX3i CPU version 3.0 or later to ensure seamless signal scaling and hardware initialization. The module manages power distribution by drawing up to 375 mA from the 3.3 VDC backplane rail alongside 160 mA from an external 24 VDC user supply.
Q: What CPU firmware level is required to operate the IC695ALG704 module in an RX3i chassis?
A: The module requires RX3i CPU firmware version 3.0 or later for valid backplane recognition and parameter configuration.
Q: What are the electrical load limitations for the current and voltage output channels?
A: Current channels drive up to 850 Ohms maximum with 10 uH maximum load reactance. Voltage channels support load reactance up to 1 uF.
Q: Does the IC695ALG704 module support HART protocol communication?
A: No, HART protocol is not supported on the analog output channels of this module.
Our production line was down due to a faulty Bently Nevada monitor. We found it in stock here and they shipped it via DHL immediately. Back in operation within 48 hours—truly a lifesaver for our plant.
Finding brand new, original modules is critical for our safety. This team delivers factory-fresh components with full certification. Their commitment to only selling new products makes them our most trusted partner.
We have sourced Honeywell and Schneider parts here for two years. Every shipment arrives well-packaged with original factory seals intact. Clear communication and the best lead times in the industry.