The GE Fanuc IC697MDL940 serves as the primary IC697MDL940 Relay output module utilized to execute discrete power switching operations across Series 90-70 platforms. Configured for routing control signals and power switching to external actuator loops, the unit establishes direct physical isolation between internal logic and field-side circuits. The device features a 16-channel array divided into eight individually isolated Form C channels and eight Form A channels segmented into two groups of four outputs.
| Parameter | Specification |
|---|---|
| Model | IC697MDL940 |
| Brand | GE Fanuc Emerson |
| Origin | USA |
| Product Line | Series 90-70 |
| Type | Relay Output Module |
| Number of Channels | 16 (8 Form C individually isolated, 8 Form A in 2 groups of 4) |
| Operating Voltage | 120/240 VAC (47-63 Hz) or 5/24/125 VDC |
| Maximum Load Current | 16 A per module, 4 A per group, 2.0 A per point (voltage dependent) |
| Minimum Load Current | 10 mA |
| Maximum Leakage Current | 1 mA at 120 VAC |
| Maximum Response Time | 10 ms (On / Off transition) |
| Switching Frequency | 20 cycles per minute maximum (inductive load) |
| Isolation Voltage | 1500 V |
| Power Consumption | 480 VA (AC loads), 60 W (DC loads), 750 mA logic current draw |
| Contact Composition | Silver alloy, fixed coil, moving armature |
| Contact Resistance | 0.2 Ohm maximum |
| Built-in Protection | 3 A fuse per channel, snubber circuit (47 Ohm + 0.015 ufd) |
| Operating Temp | 0 to 60 deg C |
| Weight | 2.00 lbs (0.91 kg) |
| Dimensions | Single-slot VME width |
Operating within the Series 90-70 VME standard architecture, the module execution speed relies directly on the backplane bus communication velocity and physical backplane interrupts. State transition data written from the CPU to the discrete output registers registers instantly at the physical interface. For deterministic networks such as Profinet or EtherNet/IP running via local or remote rack adapters, the response latency is governed by the CPU scan times. Inductive switching limits are physically capped at 20 cycles per minute to minimize contact wear and heat generation, while internal RC snubber networks (47 Ohm resistor paired with a 0.015 ufd capacitor) suppress transient high-voltage spikes.
Q: Can the Form C and Form A outputs on the IC697MDL940 be used to switch different voltage phases?
A: Yes. The eight Form C output channels are individually isolated, allowing them to switch different voltages or phases. The Form A channels are divided into two common groups of four and must share a common line voltage within their respective groups.
Q: What action must be taken if a single output channel on the module fails to close?
A: The IC697MDL940 contains internal, non-serviceable 3 A fuses for individual channel protection along with moving-armature contacts. If a short circuit occurs and the fuse blows, or if the silver alloy contacts reach their limit of electrical operations, the physical module must be serviced or replaced.
Our production line was down due to a faulty Bently Nevada monitor. We found it in stock here and they shipped it via DHL immediately. Back in operation within 48 hours—truly a lifesaver for our plant.
Finding brand new, original modules is critical for our safety. This team delivers factory-fresh components with full certification. Their commitment to only selling new products makes them our most trusted partner.