100% Genuine. 100,000+ Parts in Stock. Ready to Ship.

  • en

Configured for bipolar analog voltage processing in RX3i PACSystem platforms, the GE IC694ALG220 (IC694ALG220 Analog Input Module) provides direct physical/electrical execution. The module converts -10 VDC to +10 VDC voltage signals across 4 channels using a 12-bit analog-to-digital converter, completing a full 4-channel scan update in 4 ms.

Hardware Specifications

Parameter Specification
Model IC694ALG220
Brand GE Fanuc Emerson
Series RX3i PACSystem
Product Type Analog Input Modules
Number of Channels 4 channels
Analog Input Range -10 VDC to +10 VDC
Resolution 12 bit
Channel Conversion Speed 1 ms per channel
Module Update Rate 4 ms for all 4 channels
Input Filter Response 17 Hz
Cross-Channel Rejection Greater than 80 dB
Power Consumption 25 mA at 5 VDC; 98 mA at 24 VDC
Operating Voltage 24 VDC
Field Connection Type Screw terminals
Local Signalling Diagnostic LED indicators
Mounting Method Panel mount or DIN rail
Operating Temp 0 to +60 deg C
Dimensions Single-slot RX3i module footprint
Weight 0.28 kg (0.63 lbs)
Origin USA

Backplane Bus Interfacing and Deterministic Networks

The IC694ALG220 module connects directly to the RX3i backplane bus, transferring digitized field data to the CPU at high backplane bus communication velocity. The module processes all 4 input channels within a deterministic 4 ms refresh cycle, applying a 17 Hz input hardware filter and delivering over 80 dB of cross-channel isolation. Integrated firmware flash compatibility maintains consistent timing profiles across high I/O density scaling configurations without compromising signal fidelity.

Frequently Asked Questions

Q: What are the backplane and external power demands for the IC694ALG220 module?

A: The module draws 25 mA at 5 VDC from the internal backplane bus and requires 98 mA from an external 24 VDC power supply.

Q: How fast does the module update input values to the controller?

A: Each individual channel completes conversion in 1 ms, yielding a total scan update rate of 4 ms for all 4 channels.

Q: What mounting options are available for this RX3i module?

A: The module installs directly into any standard RX3i baseplate slot, supporting both panel mounting and DIN rail mounting chassis configurations.

Field Installation Guidelines

  1. Remove primary rack power and field 24 VDC power before inserting or removing the module from the baseplate.
  2. Fasten an ESD wrist strap to a verified enclosure earth ground before handling the unit.
  3. Align the module with the target RX3i backplane slot and press firmly until the module latches securely into the baseplate.
  4. Wire field voltage sources (-10 VDC to +10 VDC) to the removable terminal block using the integrated screw terminals, grounding cable shields at a single chassis ground point.
  5. Reapply power and verify that front-panel LED indicators show normal operational status without channel fault indications.