Configured for high-precision temperature measurement and resistance signal conversion in VersaMax system platforms, the GE Fanuc IC200ALG620 (IC200ALG620 Analog Input Module) provides direct physical/electrical execution. The module accommodates 4 RTD/resistance input channels utilizing dedicated 16-bit Analog-to-Digital Converters (ADCs) per channel to interface 3-wire and 4-wire RTD sensors or direct resistance ranges.
| Parameter | Specification |
|---|---|
| Model | IC200ALG620 |
| Brand | GE Fanuc |
| Origin | USA |
| Weight | 0.88 lbs (0.40 kg) |
| Dimensions | Single-slot VersaMax module footprint |
| Operating Temp | 0 deg C to 60 deg C |
| Power Consumption | 125 mA max at 5 VDC bus; 125 mA at 3.3 VDC bus |
| Input Channels | 4-point RTD / Resistance input channels |
| Resolution | 16 bits (15 bits plus sign) |
| Compatible RTD Types | Platinum (25, 100, 1000 ohm); Copper (10, 50, 100 ohm); Nickel (100, 120 ohm); Nickel/Iron (604 ohm) |
| Resistance Input Ranges | 0-500 Ohms; 0-3000 Ohms |
| Wiring Configurations | 3-wire and 4-wire RTDs |
| Maximum Lead Resistance | 5 Ohms per lead |
| Channel Update Rate | 210 ms at 60 Hz; 230 ms at 50 Hz |
| Measurement Accuracy | +/-0.15% on resistance; +/-0.15% on RTD temperature (at 25 deg C) |
| Temperature Sensitivity | +/-0.004% of reading; +/-1.5 uV per deg C (referred to input) |
| Isolation | 250 VAC (input to logic), 1500 VAC for 1 minute (input to frame) |
| Status Indicators | FLD PWR LED, OK LED |
The module executes internal data transfers over the VersaMax 5 VDC and 3.3 VDC logic backplane bus, drawing up to 125 mA from both supply rails. Digital conversion values are generated at a channel update rate of 210 ms at 60 Hz filter frequency or 230 ms at 50 Hz filter frequency. Onboard diagnostic firmware continuously reports channel-level conditions—including Open RTD, input short, underrange, overrange, non-volatile memory storage fault, wiring fault, and high/low alarms—directly to the host CPU controller. Front panel LED indicators signal module boot cycles, firmware updates, normal operation, and fault states.
Q: What RTD wiring configurations are supported by the IC200ALG620?
A: The module directly supports both 3-wire and 4-wire RTD sensor wiring arrangements with a maximum allowable lead resistance of 5 Ohms per lead.
Q: How does the OK LED report operational and diagnostic states?
A: A solid green OK LED indicates normal backplane power and operation, flashing green indicates firmware update or boot mode, and solid amber indicates an active module diagnostic error.
Q: What are the backplane current draw demands for this module?
A: The module draws a maximum of 125 mA at 5 VDC output and 125 mA at 3.3 VDC output from the system backplane.
Our production line was down due to a faulty Bently Nevada monitor. We found it in stock here and they shipped it via DHL immediately. Back in operation within 48 hours—truly a lifesaver for our plant.
Finding brand new, original modules is critical for our safety. This team delivers factory-fresh components with full certification. Their commitment to only selling new products makes them our most trusted partner.
We have sourced Honeywell and Schneider parts here for two years. Every shipment arrives well-packaged with original factory seals intact. Clear communication and the best lead times in the industry.