100% Genuine. 100,000+ Parts in Stock. Ready to Ship.

  • en

Configured for discrete high-speed counting and signal processing in VersaMax PLC systems, the GE Fanuc IC200UDD020 (IC200UDD020 VersaMax Micro Controller) provides direct physical/electrical execution across 12 DC inputs and 8 DC source outputs.

Hardware Specifications

Parameter Specification
Model IC200UDD020
Brand GE Fanuc Emerson
Origin USA / Various
Weight 0.33 kg (0.77 lbs)
Dimensions Standard VersaMax Micro footprint
Operating Temp 0 to 60 deg C
Power Consumption 5 W power rating
Rated Supply Voltage 24 VDC (19.2 to 30 VDC range)
Typical Input Current 0.2 A at 24 VDC
Maximum Inrush Current 1 A for 10 ms at 30 VDC
Hold-Up Time 10 ms at 19.2 VDC
Total Channel Count 20 I/O Points
Input Channel Type 12 DC inputs (positive or negative logic)
Output Channel Type 8 DC source outputs
High-Speed Counters Configurable (4 Type A, 1 Type A + 1 Type B, 4 Type A_32, or 1 Type A_32 + 1 Type B_32)
Mounting Type 35 mm DIN rail or panel mount

Backplane Bus Communication Velocity & High-Speed Counter Execution

The IC200UDD020 executes real-time logic routines while maintaining rapid backplane bus communication velocity across expanded I/O tracks. Onboard high-speed counter channels process rapid pulse streams independently of the primary scan cycle, supporting multi-mode configurations including 32-bit Type A and Type B options. Firmware flash compatibility ensures unified register allocation and seamless system synchronization when interfacing with external expansion units across the VersaMax network architecture.

Frequently Asked Questions

Q: What are the input voltage tolerances and ride-through capabilities of the IC200UDD020 power circuit?

A: The controller accepts an operational supply range of 19.2 to 30 VDC with a typical current draw of 0.2 A at 24 VDC. It provides a power supply hold-up time of 10 ms at 19.2 VDC to withstand brief line drops.

Q: How are the high-speed counter channels configured on this model?

A: The controller supports flexible high-speed counting modes, including up to four 16-bit/32-bit Type A counters or combinations of Type A and Type B counter configurations for quadrature and directional pulse decoding.

Field Installation Guidelines

  • DIN-Rail and Panel Mounting: Snap the unit onto a standard 35 mm DIN rail or secure it via panel mounting holes. Maintain a minimum vertical clearance of 50 mm above and below the module for natural thermal convection.
  • DC Power and Field I/O Wiring: Wire the 24 VDC power source to the dedicated supply terminals, keeping inrush limits under 1 A. Route low-voltage DC logic input wiring separately from high-current DC sourcing output lines to minimize electromagnetic interference.
  • System Grounding: Connect the chassis protective earth terminal directly to the enclosure ground bar using a heavy-gauge copper conductor to ensure transient noise immunity and stable counter operation.

What's clients say about us