100% Genuine. 100,000+ Parts in Stock. Ready to Ship.

  • en

The GE Fanuc IC200UEX636, also cataloged as the IC200UEX636 Analog Expansion Module, operates as a dedicated hardware component for mixed analog signal acquisition and generation within VersaMax Micro control networks. The unit incorporates 4 analog input channels and 2 analog output channels to process standard industrial voltage and current loops.

Hardware Specifications

Parameter Specification
Model IC200UEX636
Brand GE Fanuc
Origin USA
Weight 2.00 lbs (0.91 kg)
Dimensions Compact VersaMax Micro Footprint
Operating Temp 0 deg C to 60 deg C
Power Consumption 120/240 VAC nominal operating voltage
Total Built-In I/O 6 analog channels (4 inputs / 2 outputs)
Input Signal Ranges 0 to 10 VDC, -10 to 10 VDC, 0 to 20 mA, 4 to 20 mA
Output Signal Ranges 0 to 10 VDC, 0 to 20 mA, 4 to 20 mA
Conversion Resolution 12-Bit for both input and output channels
User Sensor Power Output 200 mA at 24 VDC

Backplane Bus Communication Velocity & Firmware Flash Compatibility

The analog module interfaces directly with the main VersaMax Micro controller base, scaling total system analog density via local expansion connections. Internal analog-to-digital and digital-to-analog converters execute 12-bit signal quantization, updating data registers on each scan cycle. Firmware flash compatibility within the host CPU ensures synchronized data transfer across the local expansion bus, while an onboard auxiliary supply delivers 200 mA at 24 VDC to energize external field transmitters.

Frequently Asked Questions

Q: What physical signal types can be wired to the input channels of the IC200UEX636?

A: The 4 input channels support 0 to 10 VDC, -10 to 10 VDC bipolar voltage inputs, as well as 0 to 20 mA and 4 to 20 mA current loops.

Q: Does the module provide power for external field sensors?

A: Yes, the unit includes an integrated user power supply output rated for 200 mA at 24 VDC.

Q: What digital resolution does the IC200UEX636 provide for conversion?

A: Both the 4 analog inputs and 2 analog outputs operate with 12-bit analog-to-digital and digital-to-analog conversion resolution.

Field Installation Guidelines

  1. Mount the expansion unit securely onto a standard 35 mm DIN rail adjacent to the primary VersaMax Micro controller base.
  2. Connect the expansion bus interface cable between the base unit and the IC200UEX636 module prior to energizing.
  3. Wire the main 120/240 VAC supply lines to the module power input terminals in accordance with local electrical codes.
  4. Route 4 to 20 mA and voltage analog signal lines using shielded twisted-pair cabling, grounding the shield at one end only to prevent ground loops.
  5. Verify that the total current draw from the 24 VDC auxiliary sensor output does not exceed the maximum rated 200 mA limit.