Configured for analog signal digitizing in PACSystem RX3i platforms, the GE Fanuc IC695ALG608 (IC695ALG608 Analog Input Module) provides direct physical/electrical execution.
| Parameter | Specification |
|---|---|
| Model | IC695ALG608 |
| Brand | GE Fanuc / Emerson |
| Origin | USA |
| Weight | 0.31 kg (0.69 lbs) |
| Dimensions | Standard RX3i single-slot module |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | 330 mA max at 5.0 VDC, 600 mA max at 3.3 VDC (4.83 W total dissipation) |
| Channel Count | 8 non-isolated single-ended or 4 non-isolated differential |
| Analog Ranges (Voltage) | +/-10 VDC, 0-10 VDC, +/-5 VDC, 0-5 VDC, 1-5 VDC, +/-50 mV, +/-150 mV |
| Analog Ranges (Current) | 0-20 mA, 4-20 mA, +/-20 mA |
| ADC Resolution | 24-bit converter |
| Data Format | Configurable IEEE 32-bit floating point or 16-bit integer in 32-bit field |
| Configurable Filters | 8 Hz, 12 Hz, 16 Hz, 40 Hz, 200 Hz, 500 Hz |
| Input Impedance | >100 kohms (Voltage), 249 ohms +/-1% (Current) |
| Overvoltage / Overcurrent Protection | +/-60 VDC continuous (Voltage), +/-28 mA continuous (Current) |
| Compatible Terminal Blocks | IC694TBB032, IC694TBB132, IC694TBS032, IC694TBS132 |
The IC695ALG608 transfers converted 24-bit analog data over the PCI-based RX3i backplane, maintaining fast bus communication velocity for real-time control routines. Firmware flash compatibility via Proficy Machine Edition (version 5.0 SP3 or later) enables soft configuration of per-channel ranges, scaling limits, and digital filtering options without physical jumper alterations. Built-in autocalibration routines execute on power-up to ensure accurate conversion thresholds across all active channels.
Q: What power rails does the IC695ALG608 draw from the RX3i backplane bus?
A: The module draws power directly from both the 3.3 VDC rail (up to 600 mA) and the 5.0 VDC rail (up to 330 mA), with a total maximum power dissipation of 4.83 W.
Q: How are open-circuit conditions handled on current input loops?
A: When configured for 4-20 mA or 1-5 VDC ranges, the module performs open-circuit detection with a maximum response time of 1 second, flagging diagnostic status bits in CPU memory.
Q: Can single-ended and differential configurations be mixed on the same module?
A: The module operates either as an 8-channel single-ended array or a 4-channel differential array based on hardware wiring and module software configuration.
Our production line was down due to a faulty Bently Nevada monitor. We found it in stock here and they shipped it via DHL immediately. Back in operation within 48 hours—truly a lifesaver for our plant.
Finding brand new, original modules is critical for our safety. This team delivers factory-fresh components with full certification. Their commitment to only selling new products makes them our most trusted partner.