100% Genuine. 100,000+ Parts in Stock. Ready to Ship.

  • en

The GE Fanuc IC697CPU780, also cataloged as the IC697CPU780 CPU module, operates as a dedicated hardware component for processing control logic and executing deterministic synchronization within Series 90-70 Programmable Logic Controller platforms.

Hardware Specifications

Parameter Specification
Model IC697CPU780
Brand GE Fanuc Emerson
Origin United States
Weight 1.00 lbs (0.45 kg)
Dimensions Single-slot VME form factor
Operating Temp 0 - 60 deg C
Power Consumption 1.6 Amps at 5 VDC
Microprocessor 80386DX (16 MHz)
Boolean Execution Speed 0.4 microseconds per function
Discrete I/O Capacity 12 KB
Analog I/O Capacity 8 KB
Maximum System Memory 512 KB
Integrated Communication RS485 interface via 15-pin D-connector
Battery Backup IC697ACC701 Lithium (6 months data retention)
Backplane Standard VME standard C.1 compliance

Firmware Flash Compatibility and Redundant Execution

The hardware utilizes a 16 MHz internal clock structure to manage high-speed data exchanges across the VME backplane. In redundant configurations, firmware flash compatibility between the primary and secondary units is required to maintain the 20 milliseconds scan extension limit. A firmware mismatch halts execution and prevents the one-scan bumpless transfer sequence when a transition from RUN to STOP mode occurs.

Frequently Asked Questions

Q: What is the exact operational current load drawn by the module from the backplane?

A: The module draws a constant load of 1.6 Amps from the 5 VDC backplane power rail. Power supply sizing calculations for rack 0 must account for this baseline draw alongside any adjacent bus transmitter or redundancy communication modules.

Q: How is the non-volatile memory protected during an extended power outage?

A: The system memory retains data for up to six months using the IC697ACC701 lithium battery connected to the module front face. If the battery voltage drops below the critical threshold, the "Module OK" LED status transitions to indicate a memory backup fault.

Field Installation Guidelines

  • Slot Restrictions: The module must be installed exclusively in slot 1 of rack 0 within the Series 90-70 chassis to establish mastership over the VME backplane standard C.1 communications.
  • Redundancy Communication Link: When deploying a hot-standby pair, verify that the dedicated bus transmitter modules and redundancy cards are fully seated and anchored before powering up either CPU node.
  • Battery Connection: Ensure the IC697ACC701 battery lead is securely plugged into the internal board connector prior to sliding the chassis into the frame to avoid memory parity errors on initial boot.

What's clients say about us