100% Genuine. 100,000+ Parts in Stock. Ready to Ship.

  • en

Configured for excitation I/O signal routing in GE EX2000 Excitation Control Systems, the GE IS200EMIOH1AEB (IS200EMIO Exciter Main I/O Board) provides direct physical/electrical execution. It manages 12 channels of analog signals across EPCT, ECTB, EACF, and EXTB terminal boards. Operating as a single-slot, double-height VME-style board mounted directly in the control rack, it processes 4-20 mA current loops and 0-20 mA analog output drives while maintaining a common mode voltage tolerance range of +/-5 V across field interface circuits.

Hardware Specifications

Parameter Specification
Model IS200EMIOH1AEB
Brand General Electric (GE)
Origin United States
Dimensions 8.26 cm high x 4.19 cm wide
Operating Temp -30 to 65 deg C
Power Consumption VME backplane powered
Series EX2000
Product Type Exciter Main I/O Board
Form Factor Single-slot, double-height VME-style board
Channel Count 12 channels
Input Signal Span 4-20 mA
Analog Output Current 0-20 mA
Common Mode Voltage Range +/-5 V
Maximum Lead Resistance 15 ohm
Technology Surface Mount
Terminal Board Compatibility EPCT, ECTB, EACF, EXTB

I/O Density Scaling and Signal Conditioning

The IS200EMIOH1AEB maximizes I/O density scaling within the EX2000 control rack by integrating 12 analog feedback channels into a single VME rack position. High-density surface-mount assembly enables onboard signal conditioning for 4-20 mA inputs and 0-20 mA outputs while restricting lead resistance limits to 15 ohm per channel. The electrical architecture provides low-latency execution across interconnected EPCT, ECTB, EACF, and EXTB terminal boards, ensuring deterministic analog feedback during excitation loop execution.

Frequently Asked Questions

Q: What terminal board connections interface directly with the IS200EMIOH1AEB?

A: The board interfaces directly with EPCT, ECTB, EACF, and EXTB terminal boards to route field analog feedback and control commands to the excitation processor.

Q: What is the maximum allowable loop lead resistance for the analog input channels?

A: The maximum supported lead resistance is 15 ohm per input channel to maintain signal accuracy within the specified +/-5 V common mode voltage range.

Q: What form factor and rack mounting constraints apply to this module?

A: The module is engineered as a single-slot, double-height VME-style circuit board that mounts directly into the EX2000 excitation control rack.

Field Installation Guidelines

  1. Isolate all rack power feeds and field exciter supply voltages before inserting or removing the board.
  2. Put on an electrostatic discharge (ESD) grounding wrist strap connected to bare cabinet metal prior to touching the module.
  3. Align the single-slot, double-height board with the designated top and bottom VME slot card guides.
  4. Apply firm, uniform pressure to seat the multi-pin backplane connectors completely into the rack backplane headers.
  5. Secure all interface cables connecting to the EPCT, ECTB, EACF, and EXTB terminal boards, ensuring drain wires are grounded per system wiring schematics.