Configured for high-speed network integration in industrial automation environments, the Yokogawa MDK1*B, also cataloged as the MDK1 Control Processor Module, provides direct physical/electrical execution to run complex control strategies. The board functions as the central processing unit within field control units, executing regulatory, sequence, and batch control logic directly over the internal system backplane.
| Parameter | Specification |
|---|---|
| Model | MDK1*B |
| Brand | Yokogawa |
| Origin | Japan |
| Weight | 0.35 kg |
| Dimensions | 120 mm x 25 mm x 130 mm |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | 7.5 W (calculated from 5 VDC, ~1.5 A) |
| Card Type | Control Processor Module / Printed Circuit Board |
| Processor Architecture | 32-bit RISC CPU (~200 MHz clock speed) |
| Main Memory | 64 MB (battery-backed, retains data during power loss) |
| Battery Backup Duration | Up to 72 hours (recharge time ~48 hours) |
| System Compatibility | CENTUM VP, CS 3000 |
| Communication Protocols | Vnet/IP, ESB bus, ER bus |
| Electrical Isolation | 1500 VAC (system-to-bus, 1 min) |
| Humidity Range | 5 to 95% RH (non-condensing) |
The module coordinates multi-layer network topologies by integrating field control unit processors with Vnet/IP, ESB bus, and ER bus architectures. To prevent field-side voltage spikes from damaging the internal processing circuits, the hardware maintains a 1500 VAC galvanic isolation barrier between the system logic and the communication bus. The 32-bit RISC CPU handles deterministic arithmetic operations, drawing from 64 MB of volatile main memory sustained by a 72-hour battery backup unit during primary supply interruptions. Real-time system health parameters register through channel-to-channel monitoring paths, displaying runtime states via dedicated front-panel LEDs for RUN, FAIL, and active communication routines.
Q: How does the MDK1*B maintain data integrity during a total power disruption on the 5 VDC rack supply?
A: The processor uses an onboard battery backup circuit to supply power to the 64 MB volatile main memory array when external operating power drops. The circuit retains stored regulatory parameters and batch configurations for up to 72 hours, recharging fully within 48 hours once primary rack power returns.
Q: What are the functional outcomes if a single processor module fails in a dual-redundant configuration?
A: The dual-redundant architecture pairs two identical CPU cards across the backplane bus. If the primary online unit encounters a hardware fault or triggers the front-panel FAIL LED indicator, the secondary card executes a bumpless takeover of all regulatory loops and batch logic within a single execution cycle, preventing control dropouts.