Configured for power distribution in Centum VP and ProSafe-RS control platforms, the YOKOGAWA PW482-50 (PW482 Power Supply Module) provides direct physical/electrical execution. This hardware component delivers stabilized DC power to field control units and safety systems, ensuring regulated output voltages of 24 V and 5.1 V within industrial process environments.

Suffix Breakdown & Model Matrix

Suffix Code Specification
PW482 Base Power Supply Module
-5 Standard type, no explosion protection
-E Standard type with explosion protection
0 Basic type
1 ISA Standard G3 option (-20 deg C to +70 deg C)
-50 Enhanced variant with dual regulated DC outputs (24 V / 5.1 V)

Hardware Specifications

Parameter Specification
Model PW482-50
Brand Yokogawa
Origin Japan
Weight 2.0 kg
Dimensions 199.5 mm × 190 mm × 149 mm
Operating Temp -20 deg C to +70 deg C (G3 option)
Power Consumption 230 VA
Input Voltage 220 to 240 V AC ±10%
Frequency 50/60 Hz ±3 Hz
Redundancy Dual-redundant supported (2oo2)

Process Control and DCS Connectivity

The PW482-50 utilizes dedicated backplane integration to maintain internal system stability. Unlike general-purpose industrial power supplies, this module features internal channel-to-channel isolation and surge protection specifically calibrated for Yokogawa FCU/FIO/ESB bus architectures. The unit requires specific slot placement (P1-P2) on supported base plates (A2BE1D/A2BE2D) to ensure proper galvanic isolation and backplane bus communication velocity. In dual-redundant configurations, the module manages automatic load sharing and maintains continuous voltage regulation during primary supply failure.

Frequently Asked Questions

Q: Can the PW482-50 be hot-swapped in a running system?

A: Yes, provided the system backplane supports redundant power configurations. In a dual-redundant setup (two modules installed in P1 and P2), one module may be removed or replaced without interrupting the 24 V / 5.1 V DC output to the field control unit.

Q: What is the primary difference between the base PW482 and the -50 variant?

A: The standard PW482 is designed for generic FCU/FIO unit support. The -50 suffix specifically incorporates dual regulated DC outputs (24 V / 5.1 V) required for ProSafe-RS Safety Control System (SCS) logic solvers.

Field Installation Guidelines

  1. Environmental Preparation: Ensure the mounting area is free from conductive dust and corrosive gases. The G3 rated modules are designed for high-humidity environments, but the enclosure must maintain specified IP ratings.
  2. Slot Orientation: The module must be inserted into slots P1 and P2 of the designated base plate. For single-power configurations, only slot P1 must be occupied.
  3. Grounding: Secure the module to the base plate using the integrated fastening screws to ensure a low-impedance connection to the chassis protective earth (PE).
  4. Cabling: Utilize shielded AC input cables to minimize electromagnetic interference (EMI). Maintain a minimum distance of 100 mm from high-voltage AC lines to prevent crosstalk on internal signal buses.
  5. Validation: Before applying 220-240 V AC power, verify that the module keying pins align with the base plate to prevent incorrect voltage input or mechanical misalignment.