100 % original. Más de 100 000 piezas en stock. Listas para enviar.

  • es

The GE Fanuc IC695CHS012, also cataloged as the IC695CHS012 Universal Backplane, operates as a dedicated hardware component for multi-bus signal routing and module power distribution within PACSystems RX3i control platforms.

Hardware Specifications

Parameter Specification
Model IC695CHS012
Brand GE Fanuc / Emerson
Product Line PACSystems RX3i
Product Type Universal Backplane
Number of Slots 12 Slots
Bus Architecture Dual-Bus (PCI Bus & Serial Bus)
Module Compatibility RX3i PCI, RX3i Serial, Series 90-30 I/O Modules
Power Supply Support AC and DC Power Supplies
Max Current @ 3.3 VDC 600 mA (1.98 W)
Max Current @ 5 VDC 240 mA (1.20 W)
Total Heat Dissipation 3.18 W
Hot Swap Capability Supported for standard I/O modules (Excludes CPU)
Expansion Support I/O expansion cables & remote backplane cables
Terminator Requirement External terminating resistor for remote connections
Weight 4.00 lbs (1.81 kg)
Operating Temperature 0 to 60 deg C

Backplane Bus Architecture and I/O Density Scaling

The IC695CHS012 utilizes a high-velocity dual-bus backplane architecture combining a PCI bus for high-speed RX3i modules and a serial bus for backward compatibility with Series 90-30 I/O components. This dual-structure permits dynamic scaling of I/O density across mixed-generation control topologies without requiring bus translation gateways. Expansion interface connectors allow direct interconnection with remote backplane racks using dedicated expansion cabling. Signal integrity over extended expansion distances requires a dedicated external terminating resistor attached to the final rack endpoint.

Frequently Asked Questions

Q: Can the CPU module be replaced while the backplane power remains active?

A: No. While standard PCI, serial, and Series 90-30 I/O modules support hot-swapping (hot module insertion and removal) during operational runtime, CPU modules must be powered off before removal to prevent backplane bus arbitration errors.

Q: What are the internal current load limits imposed by the backplane logic circuitry?

A: The backplane onboard logic draws a maximum current of 600 mA at 3.3 VDC (1.98 W) and 240 mA at 5 VDC (1.20 W). System designers must ensure combined I/O module consumption remains within power supply output thresholds.

Field Installation Guidelines

  • Mount the backplane securely on a flat vertical panel or standard DIN rail structure, maintaining a minimum vertical clearance of 100 mm above and below the chassis for ambient thermal convection.
  • Connect the backplane grounding terminal directly to the central panel earth ground point using copper conductor wire with a minimum gauge of 14 AWG (2.08 mm sq) to minimize EMI susceptibility.
  • Ensure that remote backplane expansion cables are equipped with an external terminating resistor plugged into the end rack to prevent high-frequency bus signal reflections.
  • Observe proper insertion alignment when seating 90-30 or RX3i modules into slots 1 through 12 to avoid physical pin deformation on the backplane connector header.