100% Genuine. 100,000+ Parts in Stock. Ready to Ship.

  • en

Foxboro FBM207C RH917GY Voltage Monitor Input Module

The Foxboro FBM207C RH917GY, also cataloged as the FBM207C Voltage Monitor/Contact Sense Input Module, operates as a dedicated hardware component for discrete voltage sensing and field contact monitoring within Foxboro I/A Series DCS networks. It accepts 16 discrete input channels from DC voltage sources, mechanical contacts, or solid-state switches via two-wire configurations. The module routes channel state updates to central fieldbus processors while maintaining 1500 VDC galvanic isolation between field terminal points and internal backplane logic.

Hardware Specifications

Parameter Specification
Model FBM207C RH917GY
Brand Foxboro (Schneider Electric)
Origin USA
Weight Standard Fieldbus Module footprint
Dimensions Standard Foxboro I/A Series baseplate slot footprint
Operating Temp -40 to +70 deg C
Power Consumption Redundant DC inputs via baseplate bus
Number of Channels 16 discrete input channels
Input Signal Types DC voltage monitor, contact sense, solid-state switch
Field Termination Voltage Supports 60 VDC, 120 VAC/125 VDC, or 240 VAC via TA pairing
Isolation 1500 VDC channel-to-logic isolation
Relative Humidity 5 to 95% non-condensing
Mounting Standard Foxboro DIN rail baseplate mounting

FOUNDATION Fieldbus / Profibus PA Connectivity & Channel-to-Channel Isolation

The Foxboro FBM207C RH917GY utilizes integrated field bus communication interfaces to execute high-speed data transfers across Foxboro I/A Series control networks. Featuring 1500 VDC channel-to-logic galvanic isolation, the module prevents high-voltage surges and field loop transients from penetrating the primary system backplane. Built-in signal conditioning logic filters contact bounce and validates voltage thresholds across all 16 channels, delivering synchronized discrete state updates directly to host DCS controllers.

Frequently Asked Questions

Q: Does the FBM207C RH917GY support live replacement while the DCS remains operational?

A: Yes, the module supports hot-swap functionality when installed on a standard Foxboro I/A Series baseplate. You can remove and replace the hardware unit without disconnecting field wiring or interrupting power to adjacent modules on the rack.

Q: What field voltage levels can be monitored using this module?

A: The module accepts direct two-wire inputs from DC voltage sources or dry contacts. When paired with specific Foxboro termination assemblies (TAs), it supports discrete field voltage levels rated at 60 VDC, 120 VAC/125 VDC, or 240 VAC.

Field Installation Guidelines

Mount the module baseplate onto a standard 35 mm DIN rail inside a NEMA 4X or IP54 industrial enclosure. Align the rear connector pins of the FBM207C RH917GY with the target baseplate slot and press firmly until the mechanical locking levers fully engage. Maintain a minimum vertical clearance of 50 mm above and below the baseplate assembly to ensure natural convective airflow across the operating temperature range of -40 to +70 deg C.

Route field contact cabling away from high-voltage AC power distribution lines to minimize inductive noise coupling. Terminate field wiring at the corresponding removable termination assembly (TA) screw terminals using copper conductors. Connect all cable drain shields to the main cabinet earth ground bar at a single point to preserve 1500 VDC galvanic isolation and ensure signal integrity.

What's clients say about us

Translation missing: en.general.search.loading