Configured for high-voltage 100 to 120 VAC discrete signal acquisition in CENTUM VP control systems, the Yokogawa ADV141-P53 (ADV141 Digital Input Module) provides direct physical/electrical execution.
| Code / Suffix | Description | Technical Implication |
|---|---|---|
| ADV141 | Base Hardware Model | 16-channel isolated digital input module (100 to 120 VAC nominal) |
| -P | Pushbutton Input Option | Enables direct pushbutton edge detection and contact monitoring |
| 5 | Display & Non-Ex Type | Includes front-panel status LEDs; non-explosion-proof specification |
| 3 | Environmental & Temp Option | Includes ISA Standard G3 conformal coating and extended operating range (-20 to 70 deg C) |
| Parameter | Specification |
|---|---|
| Model | ADV141-P53 |
| Brand | Yokogawa |
| Origin | Japan |
| Weight | 0.40 kg Net / 2.0 kg Shipping |
| Dimensions | Standard Yokogawa CENTUM VP rack-mount I/O footprint |
| Operating Temp | -20 to +70 deg C |
| Power Consumption | 330 mA at 5 VDC |
| Input Channels | 16 discrete inputs |
| Signal Type | 100 to 120 VAC, 50/60 Hz |
| Input ON Voltage Range | 85 to 132 VAC |
| Input OFF Voltage | <= 30 VAC |
| Input Current | 4.1 mA +/- 20% per channel at nominal voltage |
| Max Allowable Input Voltage | 150 VAC |
| Isolation Withstand | 2000 VAC for 1 minute (signal to system logic) |
| Response Time | <= 8 ms |
| Conformal Coating | ISA Standard G3 compliant |
The module processes discrete high-voltage field contact states across 16 isolated channels, channeling field data straight to node controllers while preventing common-mode ground loops. Incorporating channel-to-system optical isolation up to 2000 VAC withstand rating, the hardware decouples plant-floor electrical transients from sensitive backplane logic. Designed for seamless execution within process control systems, the unit maintains signal integrity across severe industrial environments through ISA Standard G3 environmental protection.
Q: Does the ADV141-P53 module allow live hot-swapping during system operation?
A: Yes. You can remove and replace an ADV141-P53 module online while the backplane remains powered, preserving continuous execution across adjacent I/O slots.
Q: How does the module handle signal isolation between field wiring and system backplane?
A: The module uses galvanic and optical isolation barriers that withstand 2000 VAC for one minute, isolating field-side AC noise and ground potential differences from system logic.
Q: What environmental conditions does the "-P53" suffix configuration protect against?
A: The suffix designates an extended operating temperature range of -20 to 70 deg C alongside ISA Standard G3 conformal coating, which shields internal circuitry from corrosive atmospheric contaminants.
Our production line was down due to a faulty Bently Nevada monitor. We found it in stock here and they shipped it via DHL immediately. Back in operation within 48 hours—truly a lifesaver for our plant.
Finding brand new, original modules is critical for our safety. This team delivers factory-fresh components with full certification. Their commitment to only selling new products makes them our most trusted partner.
We have sourced Honeywell and Schneider parts here for two years. Every shipment arrives well-packaged with original factory seals intact. Clear communication and the best lead times in the industry.