100% Genuine. 100,000+ Parts in Stock. Ready to Ship.

  • en

Product Overview

The GE IC200ALG630 serves as a high-precision temperature sensing interface for the VersaMax I/O family. This module provides seven independent channels designed to interface directly with Thermocouple types J, K, T, S, and R, or millivolt (mV) signals. We supply this product as 100% Brand New and Original, ensuring laboratory-grade accuracy for demanding industrial thermal processing environments.

Technical Specifications

Parameter Specification
Input Channels 7 Channels
Input Types Thermocouple (J, K, T, S, R) and Millivolt (mV)
Resolution 16-bit (15 bits plus sign)
Update Rate 60ms/channel (60 Hz) or 70ms/channel (50 Hz)
Voltage Accuracy ±0.2% at 25°C
Temperature Accuracy ±0.15% at 25°C
Backplane Consumption 125 mA Max (5V) / 125 mA Max (3.3V)
Isolation Optical isolation between field and backplane logic
Diagnostics LED Indicators: Green (Power OK), Amber (Module Fault)
Dimensions 110 mm x 66.8 mm x 50 mm

Engineering Advantages

  • High-Resolution Thermal Tracking: The 16-bit resolution (15 bits + sign) captures minute temperature fluctuations. This precision allows for tighter PID control loops in furnace management, chemical reactors, and plastic extrusion lines.

  • Flexible Thermocouple Support: One module handles multiple thermocouple types (J, K, T, S, R) and raw mV inputs. This versatility reduces spare part inventory requirements across diverse facility assets.

  • Integrated Noise Rejection: The module utilizes software-configurable filtering (50Hz/60Hz) to eliminate power line interference. This ensures stable temperature readings even when installed near high-power motors or variable frequency drives.

  • Compact High-Density Design: Seven channels occupy a standard VersaMax footprint, maximizing I/O density on the DIN rail. This architecture lowers total system cost by reducing the number of carriers and modules required for multi-zone heating applications.

  • Real-Time Diagnostics: The intelligent LED system immediately alerts operators to module faults or backplane power loss. Built-in diagnostics report channel errors directly to the PLC, preventing process runs based on invalid data.

FAQs

Q: Does the IC200ALG630 require external power for operation?

A: No. The module draws its operating power directly from the VersaMax backplane (5V and 3.3V rails). However, ensure your power supply module has sufficient capacity for the 125mA maximum draw per rail.

Q: How does the module handle cold junction compensation?

A: The IC200ALG630 performs internal cold junction compensation automatically when paired with the appropriate VersaMax carrier. This ensures accurate temperature calculation by accounting for the ambient temperature at the terminal block.

Q: Can I use this module for standard 4-20mA current loops?

A: No. The IC200ALG630 specifically targets Thermocouple and mV inputs. For 4-20mA or 0-10V signals, you should select the standard analog input modules from the VersaMax series, such as the IC200ALG240.

Q: What happens if a thermocouple wire breaks?

A: The module includes open-wire detection. Upon detecting a broken sensor wire, the module reports a fault status to the PLC and triggers the amber LED, allowing for immediate maintenance intervention.