Configured for multi-channel DC voltage branch isolation in Experion PKS and C300 architectures, the Honeywell FC-PDB-0824 (FC-PDB-0824 8-Channel Power Distribution Board) provides direct physical/electrical execution. The assembly splits a main 24 VDC supply rail into eight independently fused branch outputs to power field transmitters, switches, and remote I/O devices. Each channel incorporates individual fuse protection to isolate short-circuit conditions to a single loop, maintaining continuous power distribution across adjacent operating channels.
| Parameter | Specification |
|---|---|
| Model | FC-PDB-0824 |
| Brand | Honeywell |
| Origin | USA |
| Weight | 200g |
| Dimensions | 94 mm x 109 mm x 71 mm |
| Operating Temp | 0 deg C to +60 deg C (32 deg F to 140 deg F) |
| Power Consumption | Passive distribution board (Losses determined by fuse resistance) |
| Input Voltage Range | 18 VDC to 30 VDC (24 VDC nominal) |
| Output Channels | 8 independently fused outputs |
| Protection Rating | Max 2 AT (Slow-acting, 5 x 20 mm) per channel |
| Input Connector | 2-pole header (Weidmuller BVZ 7.62/02F SW) |
| Field Connector | 2-pole socket block (Weidmuller BL 5.08/2 SN OR) |
| Mounting Format | DIN EN Rails TS32 / TS35 x 7.5 (95 mm rail length) |
| Certifications | CE (UL, TUV, CSA Pending) |
The board layout provides clean DC voltage routing to field loops, preventing ground loop formation and common-mode voltage propagation across adjacent channels. By maintaining stable DC bus lines and low signal attenuation, the board supports overlay digital communications on field wiring, ensuring full compatibility with 4-20 mA HART loop protocol instruments and associated Experion PKS DCS carrier interfaces.
Q: What specific fuse type and physical size does the FC-PDB-0824 accept?
A: The board accepts 5 x 20 mm slow-acting fuses rated up to a maximum of 2 AT per individual output channel.
Q: Can the input connector accept reversed polarity power connections?
A: The input Weidmuller BVZ header features mechanical keying (KO BV/SV7.62) to physically prevent misaligned insertion or reverse-polarity wiring.
Q: Does replacing a blown channel fuse require powering down the entire input supply bus?
A: No. Because each output circuit operates through an independent fuse holder, technicians can pull and replace a blown fuse for a specific channel without interrupting the main 24 VDC bus powering the remaining seven channels.
Snap the board onto standard TS32 or TS35 x 7.5 DIN rail sections, allowing a minimum rail length of 95 mm. Secure all input power conductors to the 2-pole Weidmuller header, verifying that the mechanical keying tabs align correctly before applying torque. Connect field loop cabling to the 2-pole output socket blocks, keeping power supply cables routed separately from sensitive analog signal cables to eliminate inductive noise coupling. Ensure cabinet airflow maintains local ambient temperatures between 0 deg C and +60 deg C.
Our production line was down due to a faulty Bently Nevada monitor. We found it in stock here and they shipped it via DHL immediately. Back in operation within 48 hours—truly a lifesaver for our plant.
Finding brand new, original modules is critical for our safety. This team delivers factory-fresh components with full certification. Their commitment to only selling new products makes them our most trusted partner.
We have sourced Honeywell and Schneider parts here for two years. Every shipment arrives well-packaged with original factory seals intact. Clear communication and the best lead times in the industry.