The Yokogawa AEP7D-10, also cataloged as the AEP7D Primary Power Supply Bus Unit, serves as the primary AEP7D Power Supply Bus Unit utilized to execute power distribution from one or two independent sources across CENTUM VP / CS 3000 FIO System platforms. The hardware processes electrical feed splitting to downstream control and I/O subassemblies through redundant A/B input lines. It relies on internal bus copper rails to route high-amperage current while maintaining electrical partition from external enclosure frames.
| Parameter | Specification |
|---|---|
| Model | AEP7D-10 |
| Brand | Yokogawa |
| Platform | CENTUM VP / CS 3000 FIO System |
| Origin | Japan |
| Weight | 1.8 kg |
| Dimensions | 482.6 x 43.6 x 465.1 mm (Rack mount) |
| Operating Temp | -10 to +55 deg C |
| Power Consumption | Passive distribution bus; draws overhead from external sources |
| Input Power Supply Voltage | 100 to 120 V AC (50/60 Hz) |
| Withstanding Voltage | 1500 V AC for 1 minute |
| Max Input Current (Unit) | 20 A (Aggregate for the entire bus unit) |
| Max Input Current (per port) | 6 A |
| Output Capacity | 7 outputs per input (A and B), 14 outputs total |
| Connectors | MATE-N-LOK 5-pin connectors |
| Mounting | Rack mounting with M5 screws |
| Safety Standards | CE, CSA, EAC, RCM, KC, ATEX Type n |
The unit provides power rails for modules communicating via 4-20 mA HART loop protocol configurations, ensuring baseline voltage stability for continuous field signaling. Through physical partition layout, it provides the required channel-to-channel isolation parameters to prevent cross-talk between separate I/O racks connected to the same source. The stable voltage distribution preserves reference baselines for thermocouple modules using cold junction compensation units, protecting analog-to-digital measurement loops from power fluctuation errors.
Q: Can this unit mix an AC input source and a DC input source for dual redundancy?
A: No. The AEP7D-10 model internal circuitry and MATE-N-LOK input pins are configured specifically for 100 to 120 V AC operation. Mixing AC and DC voltage sources will cause physical damage to the module components.
Q: What is the maximum current limit allowed on an individual output connection port?
A: Each individual output connection port is rated for a maximum continuous electrical load of 6 A, provided that the total aggregate load across the entire module does not exceed 20 A.
Q: Does the unit provide active diagnostics feedback to the CENTUM VP controller?
A: This model operates as a passive mechanical bus distribution hub. Power monitoring status signals must be captured via auxiliary voltage sensing circuits attached to the downstream I/O racks.