100% Genuine. 100,000+ Parts in Stock. Ready to Ship.

  • en

Yokogawa AEP7D-10 CENTUM VP Primary Power Supply Bus Unit

The Yokogawa AEP7D-10, also cataloged as the AEP7D Primary Power Supply Bus Unit, serves as the primary AEP7D Power Supply Bus Unit utilized to execute power distribution from one or two independent sources across CENTUM VP / CS 3000 FIO System platforms. The hardware processes electrical feed splitting to downstream control and I/O subassemblies through redundant A/B input lines. It relies on internal bus copper rails to route high-amperage current while maintaining electrical partition from external enclosure frames.

Hardware Specifications

Parameter Specification
Model AEP7D-10
Brand Yokogawa
Platform CENTUM VP / CS 3000 FIO System
Origin Japan
Weight 1.8 kg
Dimensions 482.6 x 43.6 x 465.1 mm (Rack mount)
Operating Temp -10 to +55 deg C
Power Consumption Passive distribution bus; draws overhead from external sources
Input Power Supply Voltage 100 to 120 V AC (50/60 Hz)
Withstanding Voltage 1500 V AC for 1 minute
Max Input Current (Unit) 20 A (Aggregate for the entire bus unit)
Max Input Current (per port) 6 A
Output Capacity 7 outputs per input (A and B), 14 outputs total
Connectors MATE-N-LOK 5-pin connectors
Mounting Rack mounting with M5 screws
Safety Standards CE, CSA, EAC, RCM, KC, ATEX Type n

Process Control Loops and DCS Instrument Integration

The unit provides power rails for modules communicating via 4-20 mA HART loop protocol configurations, ensuring baseline voltage stability for continuous field signaling. Through physical partition layout, it provides the required channel-to-channel isolation parameters to prevent cross-talk between separate I/O racks connected to the same source. The stable voltage distribution preserves reference baselines for thermocouple modules using cold junction compensation units, protecting analog-to-digital measurement loops from power fluctuation errors.

Frequently Asked Questions

Q: Can this unit mix an AC input source and a DC input source for dual redundancy?

A: No. The AEP7D-10 model internal circuitry and MATE-N-LOK input pins are configured specifically for 100 to 120 V AC operation. Mixing AC and DC voltage sources will cause physical damage to the module components.

Q: What is the maximum current limit allowed on an individual output connection port?

A: Each individual output connection port is rated for a maximum continuous electrical load of 6 A, provided that the total aggregate load across the entire module does not exceed 20 A.

Q: Does the unit provide active diagnostics feedback to the CENTUM VP controller?

A: This model operates as a passive mechanical bus distribution hub. Power monitoring status signals must be captured via auxiliary voltage sensing circuits attached to the downstream I/O racks.

Field Installation Guidelines

  • Mounting and Fastening: Secure the hardware into the standard 19-inch rack enclosure using specified M5 mounting screws. Verify structural alignment to avoid torsion stresses on the internal bus bar matrix.
  • Grounding Requirements: Connect the dedicated protective earth terminal directly to the main copper grounding bar of the cabinet using a heavy-gauge copper strap to ensure a low-impedance path.
  • Connector Engagement: Insert the MATE-N-LOK 5-pin connectors completely until the locking tabs snap into place. Loose connections increase contact resistance and induce localized thermal hot spots.
  • Load Balancing: Distribute downstream current loads evenly between output block A and output block B to minimize thermal stresses and optimize path redundancy performance.

What's clients say about us