Configured for precise analog signal acquisition in CENTUM VP and CS 3000 DCS platforms, the Yokogawa ASI133-S00 (ASI133 Analog Input Module) provides direct physical signal processing for 16 independent input channels.
| Suffix | Description |
| ASI133 | 16-Channel Analog Input Module |
| -S00 | Standard communication configuration without additional hazardous area barriers |
| Parameter | Specification |
| Model | ASI133-S00 |
| Brand | Yokogawa |
| Origin | Japan |
| Weight | 0.5 kg |
| Dimensions | 3.3 x 13.5 x 14.7 cm |
| Operating Temp | 0 to 55 deg C |
| Power Consumption | Derived from I/O baseplate |
| Input Channels | 16 independent analog inputs |
| Signal Types | 4-20 mA DC, 1-5 V DC |
| Resolution | 16-bit A/D conversion |
| Input Impedance | 250 Ohm (current inputs) |
The ASI133-S00 maintains signal integrity through active channel-to-system bus isolation, preventing common-mode noise propagation from field transmitters. Each channel utilizes the 4-20 mA HART loop protocol to facilitate bi-directional communication between field sensors and the controller. To preserve accuracy in fluctuating temperature environments, the module employs cold junction compensation (CJC) for integrated temperature sensing and utilizes high-speed A/D conversion to minimize signal latency. Internal diagnostics monitor for circuit-open conditions and out-of-range signal values, updating the status register every 10 ms to ensure real-time loop stability.
Q: Is the ASI133-S00 compatible with hot-swapping procedures?
A: Yes, this module supports hot-replacement within FIO-equipped systems. Ensure the I/O baseplate is configured for active module insertion and removal, and verify that the system controller has acknowledged the module state change before establishing field loops.
Q: How should input loops be terminated to optimize noise rejection?
A: Utilize shielded twisted-pair cabling for all 4-20 mA signals. Terminate the shield at the cabinet ground bus bar only; avoid dual-point grounding to prevent ground loop currents from injecting noise into the high-resolution A/D converters.
Mounting: Secure the module onto the dedicated Yokogawa FIO I/O baseplate. Ensure the latching mechanism engages firmly to provide a reliable connection to the backplane power and communication rails.
Wiring Requirements: Ensure current loops do not exceed the 250 Ohm input impedance rating. For 1-5 V DC applications, ensure the source impedance remains below 1 kOhm to maintain specified measurement accuracy.
Environmental Control: Maintain ambient cabinet temperatures between 0 deg C and 55 deg C. Ensure natural convection paths are unobstructed by cable bundles or wire ducts to prevent thermal throttling of the internal processing components.
Electromagnetic Compatibility: Route analog signal wiring separately from high-voltage AC power cables and variable frequency drive (VFD) output lines. Maintain a minimum separation of 200 mm to minimize EMI coupling.
Our production line was down due to a faulty Bently Nevada monitor. We found it in stock here and they shipped it via DHL immediately. Back in operation within 48 hours—truly a lifesaver for our plant.
Finding brand new, original modules is critical for our safety. This team delivers factory-fresh components with full certification. Their commitment to only selling new products makes them our most trusted partner.
We have sourced Honeywell and Schneider parts here for two years. Every shipment arrives well-packaged with original factory seals intact. Clear communication and the best lead times in the industry.