Configured for high-accuracy signal execution in Foxboro I/A Series system architectures, the Foxboro FBM215/218 RH926SP (FBM215/218 HART Communication Output Interface Module) provides direct physical/electrical execution. This 8-channel hardware interface translates host control algorithms into 4-20 mA current signals while simultaneously managing bi-directional HART digital communication with intelligent field positioners and output transducers.
| Parameter | Specification |
|---|---|
| Model | FBM215/218 RH926SP |
| Brand | Foxboro (Schneider Electric) |
| Origin | USA |
| Weight | 0.4 lbs (0.18 kg) |
| Dimensions | Standard Foxboro FBM Modular Envelope |
| Operating Temp | -20 to +70 deg C |
| Power Consumption | Low Power Backplane Drain |
| System Compatibility | Foxboro I/A Series FBM I/O Architecture |
| Number of Channels | 8 Isolated Output Channels |
| Output Signal Format | 4-20 mA Analog with HART FSK Overlay |
| Humidity Range | 5% to 95% RH, non-condensing |
| Altitude Range | -300 to +12,000 meters |
| Contamination Class | Class G3 Harsh Environment (ISA S71.04) |
| Vibration Resistance | 7.5 m/s2 (0.75 g) from 5 to 500 Hz |
| Mounting | 32 mm and 35 mm DIN Rail Enclosures |
| Certifications | CE, UL, CSA Compliance |
The Foxboro FBM215/218 RH926SP utilizes channel-to-channel isolation across all eight output paths to prevent earth loop interferences from impairing valve positioning commands. Each loop transmits continuous 4-20 mA analog control levels while superimposing digital HART Frequency Shift Keying (FSK) signals for real-time diagnostic reporting from smart field devices. Conformal-coated circuit board subassemblies protect active components against atmospheric corrosives in ISA S71.04 Class G3 harsh industrial environments, stabilizing loop impedance across variable plant operating cycles.
Q: Does removing an individual output signal line disrupt HART communication on adjacent channels of the FBM215/218 RH926SP?
A: No, each of the eight output channels features complete channel-to-channel isolation. Circuit interruption or fault conditions on one channel do not affect analog output accuracy or HART digital signal transmission on remaining channels.
Q: What mounting hardware is required to install the FBM215/218 RH926SP within an industrial control panel?
A: The module housing clips directly onto standard 32 mm or 35 mm DIN rails inside an IP54-rated protective enclosure without requiring special adapter brackets.
Our production line was down due to a faulty Bently Nevada monitor. We found it in stock here and they shipped it via DHL immediately. Back in operation within 48 hours—truly a lifesaver for our plant.
Finding brand new, original modules is critical for our safety. This team delivers factory-fresh components with full certification. Their commitment to only selling new products makes them our most trusted partner.
We have sourced Honeywell and Schneider parts here for two years. Every shipment arrives well-packaged with original factory seals intact. Clear communication and the best lead times in the industry.