100% Genuine. 100,000+ Parts in Stock. Ready to Ship.

  • en

Schneider Electric 170ADI34000 Modicon Momentum Discrete Input Base

Configured for high-density binary signal acquisition in distributed control networks, the Schneider Electric 170ADI34000 (170ADI34000 Discrete Input Base) provides direct physical/electrical execution. This module processes 16 independent input channels, converting 24 V DC voltage states from limit switches and field sensors into logic data across Modicon Momentum backplane structures.

Hardware Specifications

Parameter Specification
Model 170ADI34000
Brand Schneider Electric
Origin France
Weight 0.20 kg
Dimensions Standard Modicon Momentum base profile
Operating Temp 0 to 60 deg C
Power Consumption 2.5 W maximum
Discrete Input Number 16 Channels
Logic Type Positive (Sink)
Rated Input Voltage 24 V DC
Input Voltage Limits 11-30 V DC (Logic 1), -3-5 V DC (Logic 0)
Nominal Input Current 8 mA at 24 V DC
Input Impedance 3 kOhm
Response Time Less than 1 ms
Isolation Integrity 500 V AC between I/O and system logic
Status Indicators 16 green channel LEDs, 1 red module error LED

Industrial Control & Deterministic Networks

The module relies on the Modicon Momentum internal communication path to maintain stable I/O density scaling inside crowded control enclosures. Technicians configure the discrete base with dedicated network adapters to achieve seamless communication over Profinet / EtherNet/IP deterministic networks, ensuring low-latency data updates. The internal controller checks the firmware flash compatibility continuously during power-up sequences to verify logic consistency and prevent corrupted execution loops on the local backplane bus.

Frequently Asked Questions

Q: How does the 170ADI34000 isolate field wiring transients from the primary controller logic?

A: The module contains internal optocouplers that establish a 500 V AC galvanic isolation barrier between the 24 V DC field terminal loops and the internal backplane logic circuitry.

Q: What indicates a hardware failure or loss of bus communication on this base?

A: The front panel activates a dedicated red error LED while dropping the channel data lines on the backplane bus, alerting the master communication adapter to flag an I/O fault status.

Field Installation Guidelines

  • Snaps the module chassis directly onto standard 35 mm DIN rails, ensuring the integrated locking clip latches completely to maintain mechanical stability.
  • Route all 24 V DC field signal wiring through separated cable channels away from high-voltage AC motor lines to eliminate electromagnetic cross-talk.
  • Strip the field wires to the specified length and tighten the terminal screws to the standard industrial torque rating to prevent loose electrical connections.
  • Maintain clear airflow gaps above and below the fan-less housing structure to allow proper heat dissipation during continuous 24/7 runtimes.

What's clients say about us