Configured for precise binary electrical execution in Modicon X80 platforms, the Schneider Electric BMXDDO1602 (BMX-DDO-1602 Discrete Output Module) provides direct physical/electrical execution.
| Parameter | Specification |
|---|---|
| Model | BMX-DDO-1602 |
| Brand | Schneider Electric |
| Product Type | Discrete Output Module |
| Origin | France |
| Weight | 0.12 kg |
| Dimensions | 32 mm x 100 mm x 86 mm |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | Max current per module 10 A |
| Channel Density | 16 discrete channels |
| Discrete Output Logic | Positive (Source) |
| Output Voltage | 24 VDC |
| Current per Channel | 0.625 A |
| Maximum Voltage Drop | <1.2 V at state 1 |
| Response Time on Output | 1.2 ms |
| Insulation Resistance | > 10 MOhm 500 VDC |
| MTBF Reliability | 410000 H |
The module dictates logic command transfer across the rack chassis while interfacing directly with Modicon M340 and M580 PAC platforms. During high-density I/O density scaling routines, the hardware preserves deterministic backplane bus communication velocity by maintaining stable physical execution profiles. Internal reverse mounted diodes deliver continuous reverse polarity protection, while dedicated diagnostic thresholds detect preactuator faults below 14 VDC to prevent false signaling states from interrupting core industrial control tasks.
Q: What are the electrical constraints regarding paralleling outputs on the BMXDDO1602?
A: Paralleling of outputs is permitted to support higher current demands, restricted to a maximum of 2 channels. Connecting more than 2 outputs in parallel violates thermal boundary limits and risks permanent damage to the internal transistor arrays.
Q: Is this module equipped with galvanic isolation between individual channels?
A: No, the 16 output channels share a common ground reference. The hardware provides 1400 VDC isolation strictly from channel-to-bus to protect the central backplane architecture, but it does not incorporate channel-to-channel isolation.
Our production line was down due to a faulty Bently Nevada monitor. We found it in stock here and they shipped it via DHL immediately. Back in operation within 48 hours—truly a lifesaver for our plant.
Finding brand new, original modules is critical for our safety. This team delivers factory-fresh components with full certification. Their commitment to only selling new products makes them our most trusted partner.
We have sourced Honeywell and Schneider parts here for two years. Every shipment arrives well-packaged with original factory seals intact. Clear communication and the best lead times in the industry.