100% Genuine. 100,000+ Parts in Stock. Ready to Ship.

  • en

Yokogawa YNT511D-V42/KT S3 Bus Repeater

The Yokogawa YNT511D-V42/KT, also cataloged as the YNT511D Bus Repeater Module, operates as a dedicated hardware component for signal amplification and transmission distance extension within V net, S3 bus, and RIO control networks.

Suffix Breakdown & Model Matrix

Model / Suffix Code Description / Specification
YNT511D S3 Bus Repeater Module
-V42/KT Hardware revision and connector specification variant

Hardware Specifications

Parameter Specification
Model YNT511D-V42/KT
Brand Yokogawa
Origin Japan
Weight 2.8 kg
Dimensions 22.5 mm (W) x 99 mm (H) x 120 mm (D)
Operating Temp -10 to +55 deg C
Power Consumption Max 60 mA at 24 VDC (Approx 110 VA at 220-240 VAC)
Input Voltage 24 VDC / 220 to 240 VAC, 50/60 Hz
Storage Temp -25 to +70 deg C
Humidity Range 5 to 95% RH (non-condensing)
Communication Distance Up to 4 km via optical interface
Isolation Voltage 1 kV DC
Protocol Compatibility V net, S3 bus, RIO network
Mounting DIN rail or panel mounting
Associated Components AIP171, AIP571, AIP578, PW502

Channel-to-Channel Isolation & Signal Integrity

The Yokogawa YNT511D-V42/KT bus repeater regenerates weak differential data signals, preventing attenuation over long-distance network segments up to 4 km. Channel-to-channel and signal-to-power electrical isolation rated at 1 kV DC protects connected CENTUM VP node cards from ground loop potential differences and high-frequency noise interference. The active optical and copper media conversion interfaces maintain low propagation delay, preserving deterministic communication loop execution across distributed control architecture lines.

Frequently Asked Questions

Q: How does the YNT511D-V42/KT module isolate system ground potential differences across long runs?

A: Internal optoelectronic decoupling provides 1 kV DC isolation between the input bus interface, output transmission lines, and internal logic circuitry, breaking ground loops over extended cable paths.

Q: What front-panel diagnostic indicators assist in field troubleshooting?

A: Integrated LEDs provide status monitoring for incoming primary 24 VDC power, active bus communication data traffic, and line fault/attenuation conditions.

Q: Can the repeater module operate with both AC and DC power supplies?

A: The module operates on a primary 24 VDC control power loop and supports system integration options utilizing 220 to 240 VAC mains excitation inputs.

Field Installation Guidelines

Engineers must follow specific physical and electrical steps when installing the YNT511D-V42/KT repeater module inside control cabinets:

  1. Mount the module vertically on standard 35 mm DIN rail or directly to cabinet backpanels, leaving 50 mm clearance above and below for passive convection cooling.
  2. Route optical fibers and field bus lines through dedicated communication raceways, physically separated from high-current AC motor leads by a minimum of 300 mm.
  3. Connect the earth ground terminal directly to the main enclosure ground bar using a short, low-impedance copper strap to optimize noise rejection.
  4. Verify supply voltage levels (24 VDC or 220-240 VAC) prior to applying power to prevent internal power supply stage damage.

What's clients say about us