Configured for high-accuracy current signal acquisition in CENTUM VP control systems, the Yokogawa SAI143-H63 S4 (SAI143 Analog Input Module) provides direct physical/electrical execution.
| Model / Suffix Code | Specification |
|---|---|
| SAI143 | Analog Input Module (4-20 mA, 16-channel, module isolation) |
| -H | HART communication support enabled type |
| 6 | Dual-redundant execution capable configuration |
| 3 | Dedicated interface connection style |
| S4 | Style code 4 hardware release revision |
| Parameter | Specification |
|---|---|
| Model | SAI143-H63 S4 |
| Brand | Yokogawa |
| Origin | Japan |
| Weight | 0.34 kg |
| Dimensions | 12.7 cm x 22.9 cm x 17.8 cm |
| Operating Temp | 0 to +55 deg C |
| Power Consumption | 320 mA at 5 VDC / 550 mA at 24 VDC |
| Input Channels | 16 channels |
| Rated Input Range | 4 to 20 mA DC |
| Permissible Input Range | 0 to 25 mA DC |
| Input Impedance | 250 ohm + current value (Power-ON) |
| Data Update Frequency | 40 ms |
| Isolation Voltage | 1500 VAC between input signal and system for 1 min |
The Yokogawa SAI143-H63 S4 analog input module processes process transmitter telemetry using integrated 4-20 mA HART loop protocol support across 16 isolated channels. Internal module isolation circuitry rated for 1500 VAC withstand voltage protects the control station backplane against field voltage surges. The unit provides dedicated transmitter power supply lines yielding 16.15 V minimum at 20 mA, allowing individual channel jumper selection for 2-wire or 4-wire current loop configurations.
Q: How is transmitter power switching configured across the input channels?
A: The onboard transmitter power supply ON/OFF function is available in 2-wire settings simultaneously for all 16 input channels.
Q: What is the minimum input impedance when the module is in a powered-off state?
A: During Power-OFF conditions, the module presents an input impedance of 500 k-ohm minimum to protect field loop current paths.
Q: Which external connection options support field wiring interface?
A: The module accommodates pressure clamp terminal blocks, MIL cable assemblies, or dedicated signal cable interface adapters.
Engineers must follow standard industrial signal wiring procedures during field setup:
Our production line was down due to a faulty Bently Nevada monitor. We found it in stock here and they shipped it via DHL immediately. Back in operation within 48 hours—truly a lifesaver for our plant.
Finding brand new, original modules is critical for our safety. This team delivers factory-fresh components with full certification. Their commitment to only selling new products makes them our most trusted partner.