Configured for 12/24 VDC discrete switching in Series 90-30 PLC and PACSystem RX3i setups, the GE Fanuc IC693MDL754 (IC693MDL754 Digital Output Module) provides direct physical/electrical execution.

Hardware Specifications

Parameter Specification
Model IC693MDL754
Brand GE Fanuc Emerson
Origin United States
Weight 0.50 lbs (0.23 kg)
Dimensions Single-slot Series 90-30 I/O form factor
Operating Temp 0 to 60 deg C (32 to 140 deg F)
Power Consumption 300 mA at 5 VDC (backplane bus)
Rated Output Voltage 12 to 24 VDC (operates up to 30 VDC)
Output Points 32 points (sourcing / positive logic)
Isolation Groups 2 isolated groups (16 points per common)
Output Current 0.75 A maximum per point
Steady-State Overcurrent Trip 5 A per point typical
Inrush Current 3 A without ESCP trip
Circuit Protection Electronic Short-Circuit Protection (ESCP) per point
Hardware Configuration Dual rear DIP switches
Fault Diagnostics Overcurrent, short-circuit, loss of field power, ESCP failure, DIP switch mismatch

Firmware Flash Compatibility and High-Density Logic Scanning

The IC693MDL754 features firmware flash compatibility across Series 90-30 CPUs and PACSystems RX3i controllers. Its 32-point high-density output layout is logically mapped into two distinct isolated groups, optimizing field wiring efficiency while maintaining high backplane bus communication velocity. Onboard hardware diagnostic routines process Electronic Short-Circuit Protection (ESCP) events, missing field voltage, and hardware DIP switch setup mismatches, pushing fault interrupts to the primary CPU within a single scan cycle.

Frequently Asked Questions

Q: What happens if an output point on the IC693MDL754 experiences a short circuit or overcurrent condition?

A: The onboard Electronic Short-Circuit Protection (ESCP) trips at a typical steady-state threshold of 5 A, isolating the affected output point and transmitting a diagnostic fault signal directly to the CPU.

Q: Are the rear DIP switch settings required to match the software configuration?

A: Yes. The dual DIP switches located on the back of the module must strictly match the software module configuration in the programming environment to prevent hardware configuration error fault alerts.

Q: What thermal derating restrictions apply when operating at higher DC field voltages?

A: No thermal derating is required when operating at 24 VDC up to 60 deg C. However, when operating at field voltages up to 30 VDC, output current must be derated for ambient operating temperatures exceeding 40 deg C (104 deg F).

Field Installation Guidelines

  1. Disconnect main power to the PLC rack chassis and turn off all external 12/24 VDC field power supplies before inserting or removing the module.
  2. Verify that the dual DIP switches on the rear circuit board are set correctly to match the system software hardware configuration before installation into the rack baseplate.
  3. Seat the module into the targeted I/O slot, pivoting the top hook into the backplate slot and pushing the bottom until the latch locks into position.
  4. Wire field output loads to the removable terminal block, ensuring positive voltage is connected to the common terminal for each 16-point group in a positive logic (sourcing) arrangement.
  5. Secure field wiring cables with proper strain relief and maintain separation from high-voltage AC cables to minimize electromagnetic interference.

 