Configured for high-density sinking load control in PACSystems RX3i backplane architectures, the GE Fanuc IC697MDL752 (IC694MDL752 Discrete Output Module) provides direct physical/electrical execution.

Hardware Specifications

Parameter Specification
Model IC694MDL752
Brand GE Fanuc Emerson
Origin USA
Weight 0.50 lbs (0.23 kg)
Dimensions Single-slot RX3i module width
Operating Temp 0 to 60 deg C
Power Consumption 1.3 Watts maximum (260 mA maximum at 5 VDC backplane bus)
Output Channels 32 discrete points (4 isolated groups of 8 channels)
Operating Voltage Range 4.75 to 5.25 VDC (TTL mode) / 10.2 to 28.8 VDC (12/24 VDC mode)
Output Current Sinking 25 mA per point (TTL mode) / 0.5 A per point (12/24 VDC mode)
Group Load Capacity 3.0 A maximum per group common / 4.0 A maximum per group
On-State Voltage Drop 0.4 VDC maximum (TTL mode) / 0.24 VDC maximum (12/24 VDC mode)
Maximum Response Time 0.5 ms (On and Off transitions)
Maximum Inrush Current 4.6 A for 10 ms
External Terminal Interface Two 24-pin Fujitsu FCN-365P024-AU connectors
Status Display 32 individually numbered green LED indicators

Backplane Bus Communication Velocity & I/O Density Scaling

The IC694MDL752 module interface is engineered to optimize backplane bus communication velocity across PACSystems RX3i chassis environments. Backplane current consumption scales dynamically up to a maximum draw of 260 mA at 5 VDC, governed by the base load plus active channel and LED status states (13 mA base + 3 mA per active channel + 4.7 mA per LED). High-density I/O scaling is achieved through two 24-pin Fujitsu connectors, enabling 32 points of isolated point-to-point output execution in a single rack slot. Firmware flash compatibility ensures seamless backplane address mapping during local CPU rack execution or within remote distributed I/O drop configurations.

Frequently Asked Questions

Q: What is the maximum allowable backplane current draw for the IC694MDL752 module from the 5 VDC rack bus?

A: The module draws up to 260 mA maximum from the 5 VDC backplane bus, calculated as 13 mA base current plus 3 mA per active channel and 4.7 mA per illuminated LED.

Q: Can different output groups on the same module operate at different voltage levels simultaneously?

A: Yes, each of the 4 isolated groups has an independent group common, allowing one group to operate in 5 VDC TTL mode while other groups run on 12 VDC or 24 VDC external user supplies.

Q: What pre-wired cabling accessories are compatible with the dual 24-pin front connectors?

A: The dual Fujitsu FCN-365P024-AU connector array interfaces directly with GE Fanuc pre-wired cable assemblies IC694CBL327 and IC694CBL328.

Field Installation Guidelines

  1. Isolate primary rack backplane power and de-energize all field load supply lines before inserting or removing the module from the RX3i chassis.
  2. Align the circuit board edges with the target RX3i backplane slot guides and slide the unit firmly into place until the rear backplane connector fully seats.
  3. Wire external DC user supplies to the group commons using correct polarity, ensuring negative logic (sinking) wiring rules are maintained across all output points.
  4. Install pre-wired cables (IC694CBL327/328) or custom harnesses onto the dual 24-pin Fujitsu connectors, ensuring side locking latches engage to prevent mechanical disconnection.
  5. Route signal wiring away from high-voltage AC cables and ground all cable shields at a single point near the enclosure entry to maintain signal integrity.