Configured for stable backplane voltage distribution in FA-M3 system architectures, the Yokogawa F3PU20-0N (F3PU20 Power Supply Module) provides direct physical/electrical execution. The unit converts wide-range AC mains input into a regulated 5 VDC system rail to power I/O boards and processor modules plugged into FA-M3 base units.
The base module hardware code designates power rating and physical build options:
| Parameter | Specification |
|---|---|
| Model | F3PU20-0N / F3PU20 |
| Brand | Yokogawa |
| Origin | Japan |
| Weight | 0.3 kg (0.66 lbs) |
| Dimensions | 102.0 mm x 102.0 mm x 76.0 mm |
| Operating Temp | 0 to +55 deg C |
| Power Consumption | 85 VA |
| Input Voltage Range | 100-240 VAC (85-264 VAC allowable, 50/60 Hz) |
| Rated Output Voltage | 5 VDC |
| Output Current | 4.3 A rated (Up to 5.0 A peak capacity) |
| Noise Immunity | 1500 Vp-p (1 us pulse width, 25-60 Hz) |
| Inrush Current | 20 A max at 120 VAC, 45 A max at 240 VAC |
The power supply module incorporates internal isolation barriers between the high-voltage AC mains input circuit and the low-voltage 5 VDC backplane bus rail. High-frequency filtering suppression reduces internal switching noise to prevent ripple voltages from coupling into adjacent analog I/O modules, maintaining loop signal accuracy across connected 4-20 mA field transmitters.
Q: What action should technicians take if total 5 VDC backplane current draw exceeds 4.3 A?
A: Calculate total module consumption across the base unit. If load requirements exceed 4.3 A, split modules across an expansion base unit utilizing a dedicated secondary power supply module.
Q: How does the F3PU20-0N module indicate normal operating power delivery?
A: A green LED illuminated on the front panel indicates stable 5 VDC output delivery to the backplane bus.
Q: Does replacing the power supply module require taking the base unit offline?
A: Yes. Power down the AC input line before unseating the module from the base unit rack to prevent arcing and internal logic damage.
Mount the power supply module onto the leftmost slot of the FA-M3 base unit (such as F3BU09-0N or F3BU13-0N), engaging the bottom hook before tightening the top retention screw to 0.8 N m torque. Connect incoming AC power lines to the dedicated terminal block, ensuring the Protective Earth (PE) terminal wires directly to the main cabinet ground bar with low-impedance copper cable. Maintain a minimum vertical clearance of 50 mm above and below the base unit to ensure adequate natural thermal convection across the module heat vents.