100% Genuine. 100,000+ Parts in Stock. Ready to Ship.

  • en

Product Overview

The Honeywell FS-TSFIRE-1624 serves as a high-integrity Field Termination Assembly (FTA) specifically engineered for the Honeywell Safety Manager (FSC) architecture. This module acts as the critical physical interface between 16 field-mounted digital fire detectors or gas sensors and the central safety controller. By converting field signals into system-ready data, it ensures rapid response times in safety-instrumented systems (SIS). We provide this unit as 100% Brand New and Original, ensuring compliance with strict industrial safety protocols.

Technical Specifications

The FS-TSFIRE-1624 utilizes a ruggedized design to maintain signal integrity in electromagnetic-heavy environments.

Specification Details
Channels 16 Digital Input Channels
Input Voltage 24 V DC (Typical)
Input Current 7 mA per channel
Safety Rating IEC 61508 SIL-Rated
Isolation Full Channel-to-System & Channel-to-Channel galvanic isolation
Operating Temp -40 °C to +70 °C
Diagnostics Open circuit, short circuit, and signal integrity monitoring
Coating Conformal coating for moisture and chemical resistance
Dimensions 9.7 cm × 35.6 cm × 53.6 cm
Weight 0.3 kg

Engineering Advantages

  • Precision Diagnostics: The module continuously monitors field wiring for open or short circuits. This proactive detection prevents "fail-to-danger" scenarios in critical fire suppression loops.

  • Extreme Environment Resilience: Featuring an operating range from -40 °C to +70 °C and specialized EMI/RFI shielding, the FS-TSFIRE-1624 performs reliably in offshore platforms, refineries, and chemical processing plants.

  • Simplified Integration: The DIN-rail mountable form factor and standard FSC cabling interface reduce installation labor and cabinet footprint.

  • High-Density Safety: Managing 16 channels on a single assembly optimizes rack space without compromising the SIL-rated safety loop requirements.

FAQs

  • Is the FS-TSFIRE-1624 compatible with non-Honeywell systems?

    No. This FTA is proprietary to the Honeywell Safety Manager (formerly FSC) platform. It requires specific Honeywell I/O cables and controller backplanes to function.

  • How does the module handle signal interference in industrial settings?

    The FS-TSFIRE-1624 incorporates hardware-level EMI/RFI shielding and channel-to-system isolation, which filters out high-frequency noise common in motor-driven environments.

  • Does this unit support line monitoring?

    Yes. When used with appropriate field resistors, the module detects and reports broken wires or short-circuits directly to the Safety Manager diagnostic buffer.

  • Is this product provided with a warranty?

    Every FS-TSFIRE-1624 we ship is 100% Brand New and includes a comprehensive 12-month factory-standard warranty.

What's clients say about us